Electrical Specifications |
Maximum voltage to earth ground |
1000 V |
Battery type |
AA alkaline IEC/EN LR6 (x4) |
Battery life |
More than 15 hours* |
* In Ground Resistance measurement mode, with backlight turned off, and RF mode turned off |
Frequency range |
40 Hz to 1 kHz |
Ingress protection |
IEC/EN 60529: IP30 with jaw closed |
LCD |
Digital reading |
9999 counts |
Refresh rate |
4 per second |
Operating temperature |
-10 °C to + 50 °C |
|
Storage temperature |
-20 °C to + 60 °C |
Operating humidity |
Non condensing (<10 °C) (< 50 °F) |
≤90% RH (at 10 °C to 30 °C [50 °F to 86 °F]) |
≤75% RH (at 30 °C to 40 °C [86 °F to 104 °F]) |
≤45% RH (at 40 °C to 50 °C [104 °F to 122 °F]) |
(Non condensing) |
Operating altitude |
2000 m (6561 feet) |
Storage altitude |
12 000 m (39,370 feet) |
Reference temperature |
23 °C ±5 °C (73 °F ±9 °F) |
Temperature coefficient |
0.15% x (specified accuracy)/ °C (<18 °C or >28 °C [<64.4 °F or >82.4 °F]) |
Overload indication |
OL |
Data logging capacity |
Minimum of 32,760 measurements |
Data logging interval |
1 second to 59 minutes and 59 seconds |
Display reading specification with standard loop resistance |
Input (Ω) |
Minimum |
Maximum |
0.474 |
0.417 |
0.531 |
0.5 |
0.443 |
0.558 |
10 |
9.55 |
10.45 |
100 |
96 |
104 |
Safety |
General |
IEC/EN 61010-1: Pollution Degree 2 IEC/EN 61557-1 |
Measurement |
IEC/EN 61010-2-032: CAT IV 600 V / CAT III 1000 V |
Current clamp for leakage current measurements |
IEC/EN 61557-13: Class 2, ≤30 A/m |
Resistance to earth |
IEC/EN 61557-5 |
Effectiveness of thepProtective measures |
IEC/EN 61557-16 |
Electromagnetic compatibility (EMC) |
International |
IEC/EN 61326-1: Portable Electromagnetic Environment |
CISPR 11: Group 1, Class B, IEC/EN 61326-2-2 |
Korea (KCC) |
Class A equipment (Industrial Broadcast & Communications Equipment) |
USA (FCC) |
47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103 |
Wireless Radio |
Frequency range |
2412 MHz to 2462 MHz |
Output power |
<10 mW |
Radio frequency certification |
FCC ID:T68-FBLE IC:6627A-FBLE |
General Specifications |
Conductor size |
40 mm (1.57 in) approximately |
Dimensions (L x W x H) |
283 x 105 x 48 mm (11.1 x 4.1 x 1.9 in) |
Weight |
880g (31 oz) |
Warranty |
One year |
Earth Ground Loop Resistance |
Range |
Accuracy1 ± (% of reading + Ω) |
0.025 Ω to 0.249 Ω |
1.5% + 0.02 Ω |
0.250 Ω to 0.999 Ω |
1.5% + 0.05 Ω |
1.000 Ω to 9.999 Ω |
1.5% + 0.10 Ω |
10.00 Ω to 49.99 Ω |
1.5% + 0.30 Ω |
50.00 Ω to 99.99 Ω |
1.5% + 0.50 Ω |
100.0 Ω to 199.9 Ω |
3.0% + 1.0 Ω |
200.0 Ω to 399.9 Ω |
5.0% + 5.0 Ω |
400 Ω to 599 Ω |
10.0% + 10 Ω |
600 Ω to 1500 Ω |
20.00% |
1 Loop resistance with no inductance, conductor centered and perpendicular to jaw |
Earth ground leakage current mA |
Autorange 50/60 Hz, True rms, crest factor CF ≤3 |
Range |
Resolution |
Accuracy1 ± (% of reading + mA) |
0.200 mA to 3.999 mA |
1 μA |
2.0% + 0.05 mA |
4.00 mA to 39.99 mA |
10 μA |
2.0% + 0.03 mA |
40.0 mA to 399.9 mA |
100 μA |
2.0% + 0.3 mA |
0.400 A to 3.999 A |
1 mA |
2.0% + 3 mA |
4.00 A to 39.99 A |
10 mA |
2.0% + 30 mA |
1 Applies to signal frequency
- 40 Hz to 1 kHz with filter set to OFF